RICHMOND HILL, ON
Ahead in the cloud – A business park for the digital age
DC3 FEATURES
-
BUILDING DESCRIPTION
Building size 106,950 SF Utility power PowerStream, 27,600 volts Parking 46 parking spaces Number of storeys 1 plus mezzanine Loading docks 2 indoor with dock levellers COMPUTER ROOM SPECIFICATIONS
Available rooms Multiple Standard critical power 1.5 MW per data hall, upgradable to 2.0 MW High density ready Yes Approximate size 10,000 SF for IT equipment Maximum cabinet space Variable 550 standard 24’W x 48”D or 330 standard 32”W x 48”D COMPUTER ROOM DENSITY
Standard density 150 watts per square foot Optional density 200 watts per square foot COMPUTER ROOM DESCRIPTION
Computer rooms Dedicated Floor height Slab on grade, 18’ building height Floor to ceiling height Base design with drop ceiling 12’6” to 13’6” Floor loading 200 pounds per square foot SECURITY
Building and perimeter Security check point for all access, ballistic glass and walls Security guards Yes, 7x24x365 Access control Yes, electronic access with dual authentication, minimum 1 biometric reader Video surveillance Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive CRITICAL POWER
Total megawatts 8 or 16 MW as required -
UPS SYSTEMS
Description High efficiency static UPS Redundancy N+1 or 2N as required GENERATORS
Description 2.5 MW diesel generator Redundancy N+1 or 2N as required ON SITE FUEL CAPACITY
Storage tanks Sub-base tanks or underground as required Fuel runtime 24 hours minimum HEAT REJECTION SYSTEMS
Description Distributed and Redundant KyotoCooling systems dedicated per data hall. Or Chilled Water solution to spec Redundancy N+1 Efficiency Annualized mechanical PUE of 1.1 or better Efficiency at utilization Unaffected by critical load utilization PDUs
Description 250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V secondary available Redundancy 2N COMMUNICATIONS
POE 2 separate network points of entry with diverse underground duct banks to metropolitan network Conduits Dedicated diverse conduits and risers to each data floor Multiple carriers Yes, data centre is carrier neutral FIRE PROTECTION
Description Double interlocked pre-action dry type sprinkler system with VESDA throughout building DESIGN PUE
Description Richmond Hill NGDCs are designed to be best in class with a PUE as low as 1.08 regardless of critical load utilization
*Some specifications listed are optional.