OVERVIEW       LOCATION       BENEFITS       FEATURES       CONTACT


MONTREAL, QC

The data centre evolved – Montreal’s only true wholesale and purpose-built data centre



NEXT GENERATION DATA CENTRE
544 RUE DE L’INSPECTEUR, MONTREAL


  • SITE
    Location 544 rue de l’Inspectuer, Montreal, Quebec
    Building size 266,671 GFA
    Transportation Montreal-Trudeau International Airport YUL
    BUILDING DESCRIPTION
    Utility power Hydro Quebec, 25,000 volts
    Parking 29 reserved underground
    Number of floors 8 plus 2 electrical/mechanical penthouse
    Loading docks 2 indoor with dock levellers
    COMPUTER ROOM SPECIFICATIONS
    Available rooms 7 dedicated data floors plus 1 half floor on ground level
    Standard critical power Up to 3.0MW per data floor
    High density ready Yes
    Approximate size 10,000 SF for IT equipment, ~20,000 GSF
    Maximum cabinet space 600 standard 24’W x 48”D or 370 standard 32”W x 48”D
    COMPUTER ROOM DENSITY
    Standard density 200 watts per square foot
    Optional density 300 watts per square foot
    COMPUTER ROOM DESCRIPTION
    Computer rooms Dedicated floor for each computer room, ~20,000 GFA
    Floor height Structural slab to slab 16’6”
    Floor to ceiling height Base design with drop ceiling 12’6” to 13’6”
    Floor loading 200+ pounds per square foot
    LEASABLE OFFICE SPACE
    Office 19,140 SF available
    Storage ~5,000 SF available in basement level
    SECURITY
    Building and perimeter Security check point for all access, ballistic glass and walls
    Security guards Yes, 7x24x365
    Access control Yes, electronic access with dual authentication, minimum 1 biometric reader
    Video surveillance Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive
  • CRITICAL POWER
    Total megawatts 21 MW
    UPS SYSTEMS
    Description High efficiency static UPS
    Redundancy N+1 or 2N as required
    GENERATORS
    Description Diesel
    Redundancy N+1 or 2N as required
    ON SITE FUEL CAPACITY
    Storage tanks 5 x 50,000 L + 1 x 30,000 L underground diesel storage
    Fuel runtime 24 hours minimum heat rejection systems
    HEAT REJECTION SYSTEMS
    Description Distributed and redundant Free Cooling systems dedicated per data floor, auxiliary chilled water available
    Redundancy N+1
    Efficiency Annualized PUE of 1.2 or better
    Efficiency at utilization Unaffected by critical load utilization
    PDUs
    Description 250 amp overhead busway, optional multiple 400 KVA PDUs, 480V primary, 400/230V secondary available
    Redundancy 2N
    COMMUNICATIONS
    POE 3 separate network points of entry with diverse underground duct banks to metropolitan network
    Conduits Dedicated diverse conduits and risers to each data floor
    Multiple carriers Yes, data centre is carrier neutral
    FIRE PROTECTION
    Description Double interlocked pre-action dry type sprinkler system with VESDA throughout building
    design pue
    DESIGN PUE
    Description Montreal NGDC is designed to be best in class with an annualized PUE of 1.20 or better regardless of critical load utilization



    *Some specifications listed are optional.

“Quebec’s power grid, the largest in North America, is one of the most reliable and most self-supporting systems in the world.”Invest Quebec