TORONTO, ON

Ahead in the cloud – A business park for the digital age



DC6 FEATURES


  • BUILDING DESCRIPTION

    Building size 200,000 SF
    Utility power Alectra, 27,600 volts
    Parking Surface parking
    Number of storeys 2
    Loading docks 3 indoor with dock levellers
    COMPUTER ROOM SPECIFICATIONS
    Available rooms Multiple
    Standard critical power 3 MW – 6MW per data hall
    High density ready Yes
    Approximate size 10,000 SF for IT equipment
    COMPUTER ROOM DENSITY
    Standard density 10-50  kW per rack
    Optional density 125+ kW per rack
    COMPUTER ROOM DESCRIPTION
    Computer rooms Dedicated
    Floor height Slab on grade, minimum 18’ building height
    Floor to ceiling height open to structure
    Floor loading 200+ pounds per square foot
    SECURITY
    Building and perimeter Security check point for all access, ballistic glass and walls
    Security guards Yes, 7x24x365
    Access control Yes, electronic access with dual authentication, minimum 1 biometric reader
    Video surveillance Yes, 7x24x365 of all exterior and interior areas, minimum 30 days of archive
    CRITICAL POWER
    Total megawatts 35 MW
  • UPS SYSTEMS
    Description High efficiency static UPS
    Redundancy N+1
    GENERATORS
    Description 3 MW diesel generator
    Redundancy N+1
    ON SITE FUEL CAPACITY
    Storage tanks Sub-base tanks
    Fuel runtime 48 hours minimum
    HEAT REJECTION SYSTEMS
    Description Distributed and Redundant Direct Evaporative Cooling systems dedicated per data hall.
    Redundancy N+1
    Efficiency Annualized mechanical PUE of 1.25 or better
    PDUs
    Description 525/600 PDUs
    Redundancy 2N
    COMMUNICATIONS
    POE 2 separate network points of entry with diverse underground duct banks to metropolitan network
    Conduits Dedicated diverse conduits and risers to each data floor
    Multiple carriers Yes, data centre is carrier neutral
    FIRE PROTECTION
    Description Double interlocked pre-action dry type sprinkler system with VESDA throughout building
    DESIGN PUE
    Description 1.3 maximum

    *Some specifications listed are optional.